足球比分007

Home | About Us | News | Products | Solution | Download | Company Qualification | Investment Cooperation | Contact Us
  
DC test products
2 MH-MPJK1 Photovoltaic DC Combiner Box Intelligent Monitoring Device Series
1 MH-PVJK2 photovoltaic DC combiner box intelligent monitoring device series
2 MH-DDC2 Multi-channel Intelligent Current Sensor Series
2 MH-SC1 handheld terminal
2

Leakage current sensor series

AC Test Products
1 MH1034 series three-phase four-wire electrical parameter acquisition module
1 MH1034-2 series two-phase three-phase four-wire electrical parameter acquisition module
1 MH912 series multi-channel single-phase electrical parameter acquisition module series
1 MH-ACJK3 Photovoltaic AC Header Intelligent Monitoring Device Series
1 MH-DDC3 24-channel AC current acquisition module series
1 MH-ACJK3 supporting infrared handset
solution
1 Data room power management system solution
1
1
More ...
Downloads
1 Manual Download
1 Solution download
1 Download
More ...
Service Hotline
1
contact details
Address: International Enterprise, No. 188, Environmental Protection Middle Road, Yuhua District, Changsha City
Center Building 1, Block A 302
Phone: 0731-82739258
Fax: 0731-82739248
Email: cs_mhkj@163.com
MH-PVJK1 Photovoltaic DC combiner box intelligent monitoring device

1

2

I. Product Performance Introduction

MH-PVJK1 photovoltaic combiner box intelligent monitoring device is a newly developed multifunctional, low power consumption and fully intelligent combiner box monitoring unit developed by our company. It has the following functions in one device:
1. Innovative "monitoring host + intelligent current sensor" mode, small size and easy installation
2. The monitoring host directly uses photovoltaic power as the working power and provides working power to the intelligent current sensor.
3. The intelligent current sensor adopts an integrated package, which has extremely high reliability.
4. The intelligent current sensor has a data interface to connect with the monitoring host.
5. Photovoltaic high voltage measurement
6.16 DC current measurement and 16 total current
7, 16-channel DC power measurement and 16-channel total power
8. One-way temperature measurement for measuring the temperature in the box (optional)
9. Two-way switch input, which can separately monitor the operation status of the lightning arrester and the main switch
10. Isolated RS485 interface is used for remote data communication and supports MODBUS-RTU protocol.
11.The infrared data interface can be conveniently used for field data inspection and parameter setting
12, built-in comprehensive protection alarm function, not only the various alarm parameters programmable settings, and each alarm function can be individually set to close or enable, convenient field application
KBT-PVX / 43.0 type photovoltaic combiner box intelligent monitoring device is small in size and easy to install. The distance between the current transformers is 18mm standard, which is the same as the width of a small circuit breaker and convenient for wiring. The use of an integrated intelligent current sensor not only improves the product Reliability also reduces the wiring in many combiner boxes; the combiner box using this device can be more neat and beautiful, and more secure.

Model description

 

Third, the outline size and terminal definition of the monitoring host

 

Terminal definition table

Terminal name

Terminal group function

Terminal description

PV +

Photovoltaic high voltage input

Photovoltaic high voltage anode

PV-

Photovoltaic high voltage anode

V +

Smart current sensor connection

Connect the smart sensor V + terminal

V-

Connect smart sensor V-terminal

A

Connect smart sensor A / TX terminal

B

Connect the smart sensor B / RX terminal

T1

temperature

Connect to temperature sensor

T2

Connect the other end of the temperature sensor

DI1

Digital input 1 (dry contact)

For connecting lightning arresters

DI2

Digital input 2 (dry contact)

For connecting circuit breakers

A

Data upload 485 interface

RS485 A

B

RS485 B

GND

RS485 common

Ground terminal

Connect the ground wire

  Four, intelligent current sensor appearance size and terminal definition diagram

Dimensions of 16 channels: 340 × 38 × 15

Dimensions of 12-way device: 268 × 38 × 15

Dimensions of 8-way device: 196 × 38 × 15

Terminal definition table

Terminal name

Terminal group function

Terminal description

V +

Smart current sensor connection

Connect to monitoring host V + terminal

V-

V-terminal of monitoring host

A / TX

Connect the monitoring host A terminal

B / RX

Connect the monitoring host B terminal

Note: The two groups of terminals on the left and right are through, either side can be connected.

Five, monitoring host technical parameters

Enter:
Working power input: DC 200 ~ 1000V, power consumption <2W
Measuring voltage range: DC 200V ~ 1000V
External switch input: dry contact input

Signal processing:
Voltage measurement: Photovoltaic voltage within the full range of 200V ~ 1000V, accuracy class 0.5, maximum error ± 5V
Temperature measurement range: -50 ℃ ~ + 125 ℃, error ± 1 ℃ (optional)

Output:
Output interface: RS-485 two-wire system ± 15KV ESD protection
Communication baud rate: 2400, 4800, 9600, 19200bps optional
Communication data format: 10 bits without parity (1 start bit, 8 data bits, 1 stop bit),
11-bit odd parity (1 start bit, 8 data bits, 1 odd parity bit, 1 stop bit)
11-bit even parity (1 start bit, 8 data bits, 1 even parity bit, 1 stop bit)
11-bit without parity (1 start bit, 8 data bits, 2 stop bits) Four data formats are optional communication protocol: standard MODBUS-RTU protocol, other protocols can be customized.
Output data: voltage, temperature inside the box Output data after connecting the smart sensor: total current, total power, average current, average power, current I, power P
Infrared output: 38KHz modulation, 2 meters range, 15 ° deflection angle

Safety:
Withstand voltage between isolated voltage photovoltaic input and case ground: 3500Vac, 60S
Withstand voltage between photovoltaic input and low-voltage main circuit: 3500Vac, 60S
Between communication interface and main circuit: 2500Vac
Working environment: working environment temperature: -25 ℃ ~ 70 ℃; storage temperature: -50 ℃ ~ 85 ℃; relative humidity: 5% ~ 95% non-condensing

Technical parameters of smart sensors  
Enter:  
Working power input: DC 4.5-5.5V current <20mA
Input rated current: DC 15A
Input current range: DC -5A to + 15A
Signal processing:  
Current measurement accuracy: 0.5 level
Output:  
Output interface: RS-485
Output data: each current
Safety:  
Isolation voltage: 5000VAC withstand voltage between current input and case ground
Normal working temperature: -30 ℃ ~ 80 ℃
Extreme storage temperature: -40 ℃ ~ 85 ℃
Relative humidity: 5% to 95% without condensation
Overload capacity: 5 times of instantaneous (<200ms) rated current without damage

Seven, the typical application description of the device

Eight, monitoring host MODBUS-RTU communication protocol description
1. The serial communication of this device fully complies with the standard MODBUS-RTU protocol. The data format, hardware timing and data frame structure fully comply with the MODBUS protocol. As long as you use our configuration special software or infrared handset to configure the device address and communication baud Rate and data format for fast and error-free communication.
2. This device supports the functional field codes in the MODBUS protocol:

function code

meaning

Features

03H

Read holding register

Read measurement data, read all setting parameters

10H

Preset multiple registers

Set communication address, baud rate, data format, various alarm parameters, etc.

3. Detailed function code

Nine, device parameter setting

1. The device address and serial port settings are registers 0040H and 0041H. For data definitions, see the attached data sheet.
2. By setting the register with address 0060H, you can choose to enable or disable various alarms
3. Each alarm parameter has been set to the optimal value when it leaves the factory, and generally does not need to be modified. For special circumstances, please refer to the attached data sheet.
4. After the alarm conditions are not met, the device will automatically exit the alarm. If the alarm conditions cannot be removed immediately and the alarm output is to be cancelled, the corresponding alarm item or all alarms can be prohibited. After the alarm conditions are removed, the alarm can be re-enabled.
5. The channel setting register is a total of 16 registers from 0050H-005FH. If the channel is not used, the corresponding register can be set to 0 to close the channel. The channel set to closed is not included in the calculation of the average value and will not be included in the channel. Call the police
6. The current deviation average alarm is mainly used to monitor the poor performance of the battery panel. When the average current is greater than the set value (default value 3A), the current deviation average alarm can be activated. The alarm rule is: when a certain current is lower than half of the average value or 1.5 times higher than the average value, an alarm is generated

X.Instructions
……………………………………………………………………………………………………………………………… ...
Home | About Us | News | Products | Solutions | Download Area | Contact Us
Copyright 2011 Changsha Dream Electronic Technology Co., Ltd. Xiang ICP No. 11003092-1 All Rights Reserved

Hunan Public Network Security No. 43011102001120

足球比分007